Chiller Performance: ashrae_901_2022_min_centrifugal

Chiller and heat pump performance data — COP, EER, kW/ton at various capacities for air-cooled, water-cooled, centrifugal, screw, scroll, and heat pump equipment per AHRI 550/590 and ASHRAE 90.1

Mechanical Engineeringequipment_type: ashrae_901_2022_min_centrifugal3 rows
equipment typecapacity tonsashrae 901 min kw per ton fl (kW/ton)ashrae 901 min kw per ton iplv (kW/ton)compressor typecop full load (dimensionless)cop iplv (dimensionless)eer full load (Btu/Wh)eer iplv (Btu/Wh)entering condenser temp F (F)kw per ton full load (kW/ton)kw per ton iplv (kW/ton)leaving chilled water F (F)notesrefrigerant
ashrae_901_2022_min_centrifugal1500.610.55centrifugal5.747.1319.5924.35850.610.5544ASHRAE 90.1-2022 Table 6.8.1-3 minimum: centrifugal water-cooled <300 tons; FL kW/ton max 0.610; IPLV kW/ton max 0.550any
ashrae_901_2022_min_centrifugal3000.560.52centrifugal6.277.5521.4125.79850.560.5244ASHRAE 90.1-2022 Table 6.8.1-3 minimum: centrifugal water-cooled 300-400 tons; FL kW/ton max 0.560; IPLV kW/ton max 0.520any
ashrae_901_2022_min_centrifugal4000.560.5centrifugal6.277.9121.4127.01850.560.544ASHRAE 90.1-2022 Table 6.8.1-3 minimum: centrifugal water-cooled >=400 tons; FL kW/ton max 0.560; IPLV kW/ton max 0.500any