Mechanical Engineeringequipment_type: chiller_centrifugal_water_cooled3 rows
equipment typecapacity tonsashrae 901 min kw per ton fl (kW/ton)ashrae 901 min kw per ton iplv (kW/ton)compressor typecop full load (dimensionless)cop iplv (dimensionless)eer full load (Btu/Wh)eer iplv (Btu/Wh)entering condenser temp F (F)kw per ton full load (kW/ton)kw per ton iplv (kW/ton)leaving chilled water F (F)notesrefrigerant
chiller_centrifugal_water_cooled1500.610.55centrifugal5.747.1319.5924.33850.610.49344Single-stage; AHRI 550/590 standard conditions; typical mid-range selection; COP=3.517/kW_per_tonR-134a
chiller_centrifugal_water_cooled2000.610.55centrifugal5.97.4520.1425.43850.5940.46344Single-stage; typical good-efficiency selection at 200-ton classR-134a
chiller_centrifugal_water_cooled3000.560.52centrifugal6.087.820.7526.63850.5770.4544Single-stage; approaching ASHRAE 90.1-2022 premium tier at 300 tonR-134a