Home/Reference Data/Chiller Performance/ashrae_901_2022_min_positive_displacement

Chiller Performance: ashrae_901_2022_min_positive_displacement

Chiller and heat pump performance data — COP, EER, kW/ton at various capacities for air-cooled, water-cooled, centrifugal, screw, scroll, and heat pump equipment per AHRI 550/590 and ASHRAE 90.1

Mechanical Engineeringequipment_type: ashrae_901_2022_min_positive_displacement3 rows
equipment typecapacity tonsashrae 901 min kw per ton fl (kW/ton)ashrae 901 min kw per ton iplv (kW/ton)compressor typecop full load (dimensionless)cop iplv (dimensionless)eer full load (Btu/Wh)eer iplv (Btu/Wh)entering condenser temp F (F)kw per ton full load (kW/ton)kw per ton iplv (kW/ton)leaving chilled water F (F)notesrefrigerant
ashrae_901_2022_min_positive_displacement750.750.6positive_displacement4.685.8615.9820.01850.750.644ASHRAE 90.1-2022 Table 6.8.1-3 minimum: water-cooled positive displacement (screw/scroll/recip) <75 tonsany
ashrae_901_2022_min_positive_displacement1500.720.56positive_displacement4.885.9816.6520.41850.720.5644ASHRAE 90.1-2022 Table 6.8.1-3 minimum: water-cooled positive displacement 75-150 tonsany
ashrae_901_2022_min_positive_displacement3000.660.54positive_displacement5.336.518.222.2850.660.5444ASHRAE 90.1-2022 Table 6.8.1-3 minimum: water-cooled positive displacement 150-300 tonsany