Home/Reference Data/Chiller Performance/chiller_screw_water_cooled

Chiller Performance: chiller_screw_water_cooled

Chiller and heat pump performance data — COP, EER, kW/ton at various capacities for air-cooled, water-cooled, centrifugal, screw, scroll, and heat pump equipment per AHRI 550/590 and ASHRAE 90.1

Mechanical Engineeringequipment_type: chiller_screw_water_cooled3 rows
equipment typecapacity tonsashrae 901 min kw per ton fl (kW/ton)ashrae 901 min kw per ton iplv (kW/ton)compressor typecop full load (dimensionless)cop iplv (dimensionless)eer full load (Btu/Wh)eer iplv (Btu/Wh)entering condenser temp F (F)kw per ton full load (kW/ton)kw per ton iplv (kW/ton)leaving chilled water F (F)notesrefrigerant
chiller_screw_water_cooled500.750.6screw4.85.616.3919.12850.7310.62644Single screw or twin screw; smallest commercial classR-134a
chiller_screw_water_cooled750.720.56screw4.955.8516.919.97850.7130.59844Twin-screw; 75-ton boundary per ASHRAE kW/ton tiersR-134a
chiller_screw_water_cooled1000.720.56screw5.16.1517.4120.99850.690.56644Twin-screw; typical light commercial plantR-134a

This is a sample. Search the full chiller performance dataset and 300+ more by creating a free account and accessing the database.