Fuse time-current characteristics, voltage ratings, interrupting capacity, and current-limiting classification by fuse class (UL 248 and IEC 60269). Also includes per-rating let-through current (peak A) and I²t (A²s) data from IEEE Std 3004.3-2020 for arc-flash and short-circuit coordination studies, covering Classes RK1, RK5, J, T (300V/600V), L, CC, G, CF, CD, C, CA, CB, mine-duty, and semiconductor fuse voltage derating.

Electrical Engineeringfuse class: CLASS T8 rowsPage 6 of 7
fuse classrecord idamp rating labelamp rating max (A)amp rating min (A)i2t 100kA A2s (A2s)peak lt 100kA A (A)standardvoltage rating V (V)
CLASS Tt600 lt 0110A110A110110100,00014,500IEEE Std 3004.3-2020600
CLASS Tt600 lt 0125A125A125125150,00015,500IEEE Std 3004.3-2020600
CLASS Tt600 lt 0150A150A150150175,00017,000IEEE Std 3004.3-2020600
CLASS Tt600 lt 0175A175A175175225,00018,500IEEE Std 3004.3-2020600
CLASS Tt600 lt 0225A225A225225350,00022,500IEEE Std 3004.3-2020600
CLASS Tt600 lt 0250A250A250250450,00024,000IEEE Std 3004.3-2020600
CLASS Tt600 lt 0300A300A300300600,00026,000IEEE Std 3004.3-2020600
CLASS Tt600 lt 0350A350A350350800,00029,000IEEE Std 3004.3-2020600