Fuse Characteristics: CLASS_L

Fuse time-current characteristics, voltage ratings, interrupting capacity, and current-limiting classification by fuse class. Covers UL 248 classes (J, RK1, RK5, CC, T, L, G, H, K) and IEC 60269 types (gG, gM, aR, aM). Includes melting and clearing I2t let-through energy ranges, peak let-through current, conventional fusing/non-fusing current factors, rejection feature type, and application guidance.

Electrical Engineeringfuse_class: CLASS_L2 rows
fuse classrecord idamp rating max (A)amp rating min (A)applicationconventional fusing current factor (dimensionless)conventional nonfusing current factor (dimensionless)current limitingdimensions ferrule bladefuse typeinterrupting rating kA ac (kA)notesrejection featuretime delayul standardvoltage rating V (V)
CLASS_Ll_600v_12016,0001,201Class L 600VAC 1201-6000A; largest UL branch-circuit fuse class; service entrance distribution switchboard; dimensional lengths increase with rating to prevent interchangeability1.350.9current_limitingknife_blade_largeL200Class L upper limit 6000A; common sizes 1201/1350/1600/2000/2500/3000/4000/5000/6000A; bolt-in blade connector; peak let-through at 100kA fault (approx): 1200A~70kA; 2000A~90kA; 4000A~120kAnone_large_blade_sizefast_actingUL_248-10600
CLASS_Ll_600v_6011,200601Class L 600VAC 601-1200A; all current-limiting; used for service entrance feeder large transformer primary; bolt-in blade design physically incompatible with lower-current classes; 200kA interrupting1.350.9current_limitingknife_blade_largeL200Class L covers 601-6000A range; physically much larger than Class J; no ferrule — knife blade only; no rejection feature needed due to unique large physical size; effective current limitation at high currentsnone_large_blade_sizefast_actingUL_248-10600

This is a sample. Search the full fuse characteristics dataset and 300+ more by creating a free account and accessing the database.

Get started for FREE

Related data