Fuse Characteristics: CLASS_C

Fuse time-current characteristics, voltage ratings, interrupting capacity, and current-limiting classification by fuse class (UL 248 and IEC 60269). Also includes per-rating let-through current (peak A) and I²t (A²s) data from IEEE Std 3004.3-2020 for arc-flash and short-circuit coordination studies, covering Classes RK1, RK5, J, T (300V/600V), L, CC, G, CF, CD, C, CA, CB, mine-duty, and semiconductor fuse voltage derating.

Electrical Engineeringfuse_class: CLASS_C3 rows
fuse classrecord idamp rating labelamp rating max (A)amp rating min (A)i2t 50kA A2s (A2s)peak lt 50kA A (A)standardvoltage rating V (V)
CLASS_Cc_lt_000_0300-3030015,00012,000IEEE Std 3004.3-2020600
CLASS_Cc_lt_031_06031-60603160,00020,000IEEE Std 3004.3-2020600
CLASS_Cc_lt_061_10061-10010061200,00030,000IEEE Std 3004.3-2020600

This is a sample. Search the full fuse characteristics dataset and 350+ more by creating a free account and accessing the database.