Fuse time-current characteristics, voltage ratings, interrupting capacity, and current-limiting classification by fuse class (UL 248 and IEC 60269). Also includes per-rating let-through current (peak A) and I²t (A²s) data from IEEE Std 3004.3-2020 for arc-flash and short-circuit coordination studies, covering Classes RK1, RK5, J, T (300V/600V), L, CC, G, CF, CD, C, CA, CB, mine-duty, and semiconductor fuse voltage derating.

Electrical Engineeringfuse class: CLASS T8 rowsPage 5 of 7
fuse classrecord idamp rating labelamp rating max (A)amp rating min (A)i2t 100kA A2s (A2s)peak lt 100kA A (A)standardvoltage rating V (V)
CLASS Tt600 lt 0025A25A25255,5006,000IEEE Std 3004.3-2020600
CLASS Tt600 lt 0035A35A353512,0007,500IEEE Std 3004.3-2020600
CLASS Tt600 lt 0040A40A404017,0008,000IEEE Std 3004.3-2020600
CLASS Tt600 lt 0045A45A454518,0008,500IEEE Std 3004.3-2020600
CLASS Tt600 lt 0050A50A505022,0009,000IEEE Std 3004.3-2020600
CLASS Tt600 lt 0070A70A707050,00011,500IEEE Std 3004.3-2020600
CLASS Tt600 lt 0080A80A808060,00012,500IEEE Std 3004.3-2020600
CLASS Tt600 lt 0090A90A909075,00013,500IEEE Std 3004.3-2020600