Fuse Characteristics: CLASS_CD
Fuse time-current characteristics, voltage ratings, interrupting capacity, and current-limiting classification by fuse class (UL 248 and IEC 60269). Also includes per-rating let-through current (peak A) and I²t (A²s) data from IEEE Std 3004.3-2020 for arc-flash and short-circuit coordination studies, covering Classes RK1, RK5, J, T (300V/600V), L, CC, G, CF, CD, C, CA, CB, mine-duty, and semiconductor fuse voltage derating.
| fuse class | record id | amp rating label | amp rating max (A) | amp rating min (A) | i2t 100kA A2s (A2s) | i2t 200kA A2s (A2s) | i2t 50kA A2s (A2s) | peak lt 100kA A (A) | peak lt 200kA A (A) | peak lt 50kA A (A) | standard | voltage rating V (V) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CLASS_CD | cd_lt_031_060 | 31-60 | 60 | 31 | 30,000 | 30,000 | 30,000 | 10,000 | 16,000 | 8,000 | IEEE Std 3004.3-2020 | 600 |