H30-110 to H30-130

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment type: Water Heater2 rows
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
Water HeaterH30-110Water heater, domestic hot0.0198431929.64441,4570.829.64IEEE Std 3006.8-2018 Table 2USACE PREP957.5
Water HeaterH30-130Water heater, domestic hot0.056516259.11155,0001.353.53IEEE Std 3006.8-2018 Table 2USACE PREP442.4