Equipment Failure Rates: Boiler

H08-100 to H08-220

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment type: Boiler3 rows
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
BoilerH08-100Boiler, hot water0.2680556886.8932,6806.353.94IEEE Std 3006.8-2018 Table 2USACE PREP2,566.6
BoilerH08-210Boiler, steam, high pressure,0.8284347816.8410,5745.5239.77IEEE Std 3006.8-2018 Table 2USACE PREP942.7
BoilerH08-220Boiler, steam, low pressure, ≤0.44609872140.8619,63748.0313.25IEEE Std 3006.8-2018 Table 2USACE PREP1,616.2