equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
Air Handling UnitH05-110AAir handling unit, humid, pan0.02769600429,88200IEEE Std 3006.8-2018 Table 2USACE PREP25
Air Handling UnitH05-120AAir handling unit, humid, spray0.01820500653,97600IEEE Std 3006.8-2018 Table 2USACE PREP38.1
Air Handling UnitH05-130Air handling unit, humid, pan0.140976302.9462,1382.733.02IEEE Std 3006.8-2018 Table 2USACE PREP212.8
Air Handling UnitH05-140Air handling unit, humid, spray0.368256384.3123,7881.592.27IEEE Std 3006.8-2018 Table 2USACE PREP103.2
Air Handling UnitH05-210Air handling unit, non-humid,0.2217091,7342.439,5111.884.95IEEE Std 3006.8-2018 Table 2USACE PREP7,821.1
Air Handling UnitH05-220Air handling unit, non-humid,0.1393814002.3662,8491.514.18IEEE Std 3006.8-2018 Table 2USACE PREP2,869.8
Air Handling UnitH05-310Air handling unit, multizone0.4058924489.9721,5824.346.18IEEE Std 3006.8-2018 Table 2USACE PREP1,103.7