Equipment Failure Rates: Accumulator

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment_type: Accumulator2 rows
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
AccumulatorH01-100Accumulator, pressurized0.00652571.011,342,5020.9610.29IEEE Std 3006.8-2018 Table 2USACE_PREP1,072.8
AccumulatorH01-200Accumulator, unpressurized0.00768430.421,140,1040.332IEEE Std 3006.8-2018 Table 2USACE_PREP390.4