Equipment Failure Rates: Water_Cooling_Coil

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment_type: Water_Cooling_Coil1 row
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
Water_Cooling_CoilH29-100Water cooling coil, fan coil unit0.005972962.091,466,9322.043.72IEEE Std 3006.8-2018 Table 2USACE_PREP16,076

This is a sample. Search the full equipment failure rates dataset and 350+ more by creating a free account and accessing the database.