Equipment Failure Rates: Capacitor_Capacitor_Bank

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment_type: Capacitor_Capacitor_Bank1 row
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
Capacitor_Capacitor_BankE10-000Capacitor/capacitor bank, all0.0509521043.13171,9274.272.37IEEE Std 3006.8-2018 Table 2USACE_PREP2,041.1

This is a sample. Search the full equipment failure rates dataset and 350+ more by creating a free account and accessing the database.

Get started for FREE