Equipment Failure Rates: Uninterruptible Power Supply

E39-100 to E39-320A

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment type: Uninterruptible Power Supply4 rows
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
Uninterruptible Power SupplyE39-100Uninterruptible power supply0.01484827.81589,9686.118.75IEEE Std 3006.8-2018 Table 2USACE PREP134.7
Uninterruptible Power SupplyE39-200Uninterruptible power supply (UPS), small computer room floor0.056576413.74154,8372.126.25IEEE Std 3006.8-2018 Table 2USACE PREP724.7
Uninterruptible Power SupplyE39-310Uninterruptible power supply0.0615792213.83142,2571.092.93IEEE Std 3006.8-2018 Table 2USACE PREP357.3
Uninterruptible Power SupplyE39-320AUninterruptible power supply0.0429901.3276,9411.3IEEE Std 3006.8-2018 Table 2USACE PREP16.1