Equipment Failure Rates: Transducer

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment_type: Transducer3 rows
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
TransducerC16-100Transducer, flow0.00420951.182,081,4001.172IEEE Std 3006.8-2018 Table 2USACE_PREP1,188
TransducerC16-200Transducer, pressure0.01309283.07669,2022.287.5IEEE Std 3006.8-2018 Table 2USACE_PREP2,139
TransducerC16-300Transducer, temperature0.002089480.034,193,5630.021.89IEEE Std 3006.8-2018 Table 2USACE_PREP22,978.4

This is a sample. Search the full equipment failure rates dataset and 350+ more by creating a free account and accessing the database.

Get started for FREE

Related data