Equipment Failure Rates: Switchgear

E36-110 to E36-300A

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment type: Switchgear7 rows
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
SwitchgearE36-110Switchgear, bare bus, ≤ 600 V0.009224234.35949,7294.287.91IEEE Std 3006.8-2018 Table 2USACE PREP2,493.6
SwitchgearE36-120Switchgear, bare bus, > 600 V0.0047649.671,840,5186.59195.75IEEE Std 3006.8-2018 Table 2USACE PREP840.4
SwitchgearE36-130Switchgear, bare bus, > 5 kV0.016746151.3523,1051.282.27IEEE Std 3006.8-2018 Table 2USACE PREP895.7
SwitchgearE36-210ASwitchgear, insulated bus, ≤0.00137203.188,677,2243.18IEEE Std 3006.8-2018 Table 2USACE PREP505.2
SwitchgearE36-220Switchgear, insulated bus, >0.00492920.781,777,2720.775IEEE Std 3006.8-2018 Table 2USACE PREP405.8
SwitchgearE36-230Switchgear, insulated bus, > 50.003738314.432,343,76014.0137.33IEEE Std 3006.8-2018 Table 2USACE PREP802.7
SwitchgearE36-300ASwitchgear, load center (free0.00086200.5913,815,2000.59IEEE Std 3006.8-2018 Table 2USACE PREP804.3