Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Equipment Failure Rates: Switch

E34-110 to E34-510A

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment type: Switch10 rowsPage 1 of 2
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
SwitchE34-110Switch, automatic transfer, ≤0.026194278.32334,4298.982.66IEEE Std 3006.8-2018 Table 2USACE PREP1,030.8
SwitchE34-120Switch, automatic transfer, ≤0.039937742.42219,3471.829.9IEEE Std 3006.8-2018 Table 2USACE PREP1,852.9
SwitchE34-211Switch, disconnect, enclosed, ≤0.00071762.0912,224,1242.09IEEE Std 3006.8-2018 Table 2USACE PREP8,372.7
SwitchE34-212Switch, disconnect, enclosed,0.00089323.389,805,7763.0346IEEE Std 3006.8-2018 Table 2USACE PREP2,238.8
SwitchE34-213Switch, disconnect, enclosed, >0.007173152.861,221,2772.0815.82IEEE Std 3006.8-2018 Table 2USACE PREP2,091.2
SwitchE34-221ASwitch, disconnect, fused, dc, ≤0.0001200.5499,372,0470.54IEEE Std 3006.8-2018 Table 2USACE PREP5,785.4
SwitchE34-222ASwitch, disconnect, fused, dc, >0.000805014,797,365IEEE Std 3006.8-2018 Table 2USACE PREP861.5
SwitchE34-310Switch, electric, on/off breaker0.00064220.0113,644,6840.011IEEE Std 3006.8-2018 Table 2USACE PREP3,115.2
SwitchE34-400Switch, float, electric0.0346118722.86253,0980.919.84IEEE Std 3006.8-2018 Table 2USACE PREP2,513.6
SwitchE34-510ASwitch, manual transfer, ≤ 6000.002604,579,482IEEE Std 3006.8-2018 Table 2USACE PREP266.6

What else is in Engineering Database