Equipment Failure Rates: Relay

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment_type: Relay3 rows
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
RelayE33-110Relay, electromechanical,0.00241524.513,627,2404.2835.5IEEE Std 3006.8-2018 Table 2USACE_PREP828.1
RelayE33-120ARelay, electromechanical,0.000877013,576,000IEEE Std 3006.8-2018 Table 2USACE_PREP790.4
RelayE33-130Relay, electromechanical,0.00081333.3610,771,4003.358IEEE Std 3006.8-2018 Table 2USACE_PREP3,688.8

This is a sample. Search the full equipment failure rates dataset and 350+ more by creating a free account and accessing the database.