equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
RecloserE31-099ARecloser (interrupter),0.0040231452,177,51155IEEE Std 3006.8-2018 Table 2USACE PREP3,480
RecloserE31-100Recloser (interrupter),0.006669131,313,572IEEE Std 3006.8-2018 Table 2USACE PREP1,949.4
RecloserE31-200Recloser (interrupter),0.019734588443,9018IEEE Std 3006.8-2018 Table 2USACE PREP2,939.1