Equipment Failure Rates: Motor_Starter

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment_type: Motor_Starter2 rows
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
Motor_StarterE28-100Motor starter, ≤ 600 V0.007987281.661,096,7470.723.37IEEE Std 3006.8-2018 Table 2USACE_PREP3,505.6
Motor_StarterE28-200Motor starter, > 600 V0.00907150.87965,6830.489.15IEEE Std 3006.8-2018 Table 2USACE_PREP551.2