| equipment type | class code | description | failure rate per year (failures/year) | failures (count) | mdt hours (h) | mtbf hours (h) | mttm hours (h) | mttr hours (h) | standard | survey | unit years (unit-years) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Inverter | E25-000 | Inverter, all types | 0.062079 | 38 | 7.59 | 141,110 | 3.93 | 17.45 | IEEE Std 3006.8-2018 Table 2 | USACE_PREP | 612.1 |