Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Equipment Failure Rates: Generator

E20-000 to E23-000

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment type: Generator6 rowsPage 2 of 2
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
GeneratorE20-000Generator, hydro turbine0.2987927310.2129,318238.4478.36IEEE Std 3006.8-2018 Table 2USACE PREP90.4
GeneratorE21-110Generator, natural gas, < 2500.67492651.512,9791.5IEEE Std 3006.8-2018 Table 2USACE PREP7.4
GeneratorE21-120Generator, natural gas, < 2500.1394193134.662,83232.876.33IEEE Std 3006.8-2018 Table 2USACE PREP222.4
GeneratorE21-210generator, natural gas, ≥ 2504.14069121471.132,116191.73IEEE Std 3006.8-2018 Table 2USACE PREP51.7
GeneratorE22-000Generator, steam turbine1.107687130263.617,908288.24100.59IEEE Std 3006.8-2018 Table 2USACE PREP117.4
GeneratorE23-000Generator, steam, heat recovery4.1858918645.842,093162.4IEEE Std 3006.8-2018 Table 2USACE PREP20.5

What else is in Engineering Database

Related data