Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Equipment Failure Rates: Fuse

E17-100A to E17-300

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment type: Fuse3 rows
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttr hours (h)standardsurveyunit years (unit-years)
FuseE17-100AFuse, 0 kV to 5 kV0.000369032,271,812IEEE Std 3006.8-2018 Table 2USACE PREP1,878.8
FuseE17-200AFuse, > 5 kV ≤ 15 kV0.000193061,672,329IEEE Std 3006.8-2018 Table 2USACE PREP3,590.5
FuseE17-300Fuse, > 15 kV0.101541483486,2704IEEE Std 3006.8-2018 Table 2USACE PREP4,756.7