Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Equipment Failure Rates: Fan

H19-100 to H19-400

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment type: Fan4 rows
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
FanH19-100Fan, centrifugal0.0485055773.57180,6001.7110.51IEEE Std 3006.8-2018 Table 2USACE PREP11,895.7
FanH19-200Fan, propeller/disc0.1682376494.3752,0692.0910.88IEEE Std 3006.8-2018 Table 2USACE PREP3,857.7
FanH19-300Fan, tubeaxial0.030738694.09284,9924.045.51IEEE Std 3006.8-2018 Table 2USACE PREP2,244.8
FanH19-400Fan, vaneaxial0.1485162541.6158,9841.114.24IEEE Std 3006.8-2018 Table 2USACE PREP1,710.3