Electrical Engineeringequipment type: Evaporator2 rows
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
EvaporatorH18-100Evaporator, direct expansion,0.004358310.292,010,3120.2714.55IEEE Std 3006.8-2018 Table 2USACE PREP7,114.1
EvaporatorH18-120Evaporator, direct expansion,0.00868790.31,008,4610.285.17IEEE Std 3006.8-2018 Table 2USACE PREP1,036.1