equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
Distribution PanelE13-100Distribution panel, ≤ 225 A,0.0038152510.92,296,0361.4122.69IEEE Std 3006.8-2018 Table 2USACE PREP6,552.6
Distribution PanelE13-200Distribution panel, > 225 A,0.004327614.342,024,27210.0616IEEE Std 3006.8-2018 Table 2USACE PREP1,386.5