Electrical Engineeringequipment type: Direct Fired Furnace2 rows
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
Direct Fired FurnaceH17-100Direct fired furnace, ≤ 5000.03717363.82235,6523.330.83IEEE Std 3006.8-2018 Table 2USACE PREP161.4
Direct Fired FurnaceH17-200Direct fired furnace, >5000.3492339824.925,08415.693.67IEEE Std 3006.8-2018 Table 2USACE PREP1,139.6