Equipment Failure Rates: Cooling Tower

H14-100 to H14-400

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment type: Cooling Tower4 rows
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
Cooling TowerH14-100Cooling tower, atmospheric type (w/o fans, motors, and internal lift pump)0.074138241.14118,1580.9988.92IEEE Std 3006.8-2018 Table 2USACE PREP323.7
Cooling TowerH14-200Cooling tower, evaporative type (w/o fans, motors, and internal lift pump)0.00582131.461,504,8001.4416.67IEEE Std 3006.8-2018 Table 2USACE PREP515.3
Cooling TowerH14-300Cooling tower, atmospheric type (with fans, motors, and internal lift pump)0.4839065028.2818,1034.348.77IEEE Std 3006.8-2018 Table 2USACE PREP1,037.4
Cooling TowerH14-400Cooling tower, evaporative type (with fans, motors, and internal lift pump)0.144195274.7860,7513.836.25IEEE Std 3006.8-2018 Table 2USACE PREP187.2