Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Equipment Failure Rates: Compressor

H11-010 to H11-100

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment type: Compressor3 rows
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
CompressorH11-010Compressor, refrigerant, ≤ 10.0267821.53327,1081.319IEEE Std 3006.8-2018 Table 2USACE PREP74.7
CompressorH11-020Compressor, refrigerant, > 10.00475350.931,843,1380.913.5IEEE Std 3006.8-2018 Table 2USACE PREP1,052
CompressorH11-100Compressor, refrigerant, screw0.055166121.15158,7940.9410.83IEEE Std 3006.8-2018 Table 2USACE PREP217.5