Equipment Failure Rates: Chiller

H10-100 to H10-510

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment type: Chiller9 rowsPage 1 of 2
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
ChillerH10-100Chiller, absorption0.158231930.7255,3620.6811.4IEEE Std 3006.8-2018 Table 2USACE PREP587.7
ChillerH10-210Chiller, centrifugal, ≤ 600 tons1.959149298140.34,47129.585.75IEEE Std 3006.8-2018 Table 2USACE PREP152.1
ChillerH10-220Chiller, centrifugal, 600 tons to0.119797795.5173,1235.2811.81IEEE Std 3006.8-2018 Table 2USACE PREP659.4
ChillerH10-230Chiller, centrifugal, > 10000.62573315235.4414,00035.179.23IEEE Std 3006.8-2018 Table 2USACE PREP242.9
ChillerH10-321Chiller, reciprocating, closed,0.1576331392.0655,5721.5311.11IEEE Std 3006.8-2018 Table 2USACE PREP881.8
ChillerH10-331Chiller, reciprocating, open,0.185496533.847,2252.9810.02IEEE Std 3006.8-2018 Table 2USACE PREP285.7
ChillerH10-410Chiller, rotary, 600 tons to0.154755149.7956,6068.748.6IEEE Std 3006.8-2018 Table 2USACE PREP90.5
ChillerH10-420Chiller, rotary, < 600 tons0.03124511.6280,3681.631IEEE Std 3006.8-2018 Table 2USACE PREP32
ChillerH10-510Chiller, screw, ≤ 300 tons0.76149838015.7111,50427.445.37IEEE Std 3006.8-2018 Table 2USACE PREP499