Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Equipment Failure Rates: Cable

E06-111 to E06-221

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment type: Cable10 rowsPage 1 of 2
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
CableE06-111Cable, ac, 0 V to 600 V, above0.000068213.0128,959,93213.068IEEE Std 3006.8-2018 Table 2USACE PREP29,442.9
CableE06-112ACable, ac, 0 V to 600 V, above0.0435450273,412IEEE Std 3006.8-2018 Table 2USACE PREP15.9
CableE06-113Cable, ac, 0 V to 600 V, above0.0001240.0872,896,9040.052.5IEEE Std 3006.8-2018 Table 2USACE PREP33,286.3
CableE06-121Cable, ac, 0 V to 600 V, below0.00012552.7970,080,7300.7316.4IEEE Std 3006.8-2018 Table 2USACE PREP40,000.4
CableE06-122Cable, ac, 0 V to 600 V, below0.0020064928.224,366,91987.7111.22IEEE Std 3006.8-2018 Table 2USACE PREP24,426.8
CableE06-123Cable, ac, 0 V to 600 V, below0.025846807.6338,9377.6IEEE Std 3006.8-2018 Table 2USACE PREP3,095.3
CableE06-211Cable, ac, 601 kV to 15 kV,0.00053728116.1116,315,31540.518.56IEEE Std 3006.8-2018 Table 2USACE PREP523,356.6
CableE06-212ACable, ac, 601 kV to 15 kV,0.00384903,093,176IEEE Std 3006.8-2018 Table 2USACE PREP180.1
CableE06-214Cable, ac, 601 kV to 15 kV,0.0007562411,589,5644IEEE Std 3006.8-2018 Table 2USACE PREP2,646
CableE06-221Cable, ac, 601 kV to 15 kV,0.0023564641.553,718,331211.4315.7IEEE Std 3006.8-2018 Table 2USACE PREP19,525.5