Cooling Load Factors: wall cts
number 41 to number 50
ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.
| factor type | item id | assembly number (dimensionless) | ctf h00 pct | ctf h01 pct | ctf h02 pct | ctf h03 pct | ctf h04 pct | ctf h05 pct | ctf h06 pct | ctf h07 pct | ctf h08 pct | ctf h09 pct | ctf h10 pct | ctf h11 pct | ctf h12 pct | ctf h13 pct | ctf h14 pct | ctf h15 pct | ctf h16 pct | ctf h17 pct | ctf h18 pct | ctf h19 pct | ctf h20 pct | ctf h21 pct | ctf h22 pct | ctf h23 pct | description | total R m2K per W ((m2·K)/W) | u value W per m2K (W/(m2·K)) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| wall cts | number 41 | 41 | 0.3 | 4.7 | 12.7 | 15 | 13.5 | 11.1 | 8.9 | 7.1 | 5.6 | 4.5 | 3.6 | 2.8 | 2.3 | 1.8 | 1.4 | 1.1 | 0.9 | 0.7 | 0.6 | 0.5 | 0.4 | 0.3 | 0.2 | 0.2 | LW CMU R-1.9 Batt Insulation Gyp. Board | 2.65 | 0.377 |
| wall cts | number 42 | 42 | 0.3 | 3.2 | 10.7 | 14.1 | 13.3 | 11.3 | 9.2 | 7.5 | 6.1 | 4.9 | 4 | 3.2 | 2.6 | 2.1 | 1.7 | 1.4 | 1.1 | 0.9 | 0.7 | 0.6 | 0.5 | 0.4 | 0.3 | 0.2 | LW CMU R-3.9 Batt Insulation Gyp. Board | 4.59 | 0.218 |
| wall cts | number 43 | 43 | 0.6 | 1.7 | 5.8 | 9.4 | 10.5 | 10.1 | 9.1 | 8 | 6.9 | 5.9 | 5.1 | 4.4 | 3.8 | 3.2 | 2.8 | 2.4 | 2.1 | 1.8 | 1.5 | 1.3 | 1.1 | 1 | 0.8 | 0.7 | LW CMU w/Fill Insulation R-1.9 Batt Insulation Gyp. Board | 3.01 | 0.332 |
| wall cts | number 44 | 44 | 0.8 | 1.4 | 4.6 | 8.1 | 9.6 | 9.6 | 8.9 | 7.9 | 7 | 6.1 | 5.4 | 4.7 | 4.1 | 3.6 | 3.1 | 2.7 | 2.4 | 2.1 | 1.8 | 1.6 | 1.4 | 1.2 | 1.1 | 0.9 | LW CMU w/Fill Insulation R-3.9 Batt Insulation Gyp. Board | 4.95 | 0.202 |
| wall cts | number 45 | 45 | 0.5 | 2.8 | 8.6 | 11.7 | 11.6 | 10.4 | 8.9 | 7.5 | 6.4 | 5.4 | 4.5 | 3.8 | 3.2 | 2.7 | 2.3 | 1.9 | 1.6 | 1.4 | 1.2 | 1 | 0.8 | 0.7 | 0.6 | 0.5 | Stucco 200 mm HW CMU R-1.9 Batt Insulation Gyp. Board | 2.42 | 0.413 |
| wall cts | number 46 | 46 | 0.5 | 2 | 7.3 | 11 | 11.4 | 10.4 | 9.1 | 7.7 | 6.6 | 5.6 | 4.8 | 4 | 3.4 | 2.9 | 2.5 | 2.1 | 1.8 | 1.5 | 1.3 | 1.1 | 0.9 | 0.8 | 0.7 | 0.6 | Stucco 200 mm HW CMU R-3.9 Batt Insulation Gyp. Board | 4.36 | 0.229 |
| wall cts | number 47 | 47 | 0.6 | 9.3 | 19.5 | 19.2 | 15 | 10.9 | 7.7 | 5.4 | 3.8 | 2.6 | 1.8 | 1.3 | 0.9 | 0.6 | 0.4 | 0.3 | 0.2 | 0.1 | 0.1 | 0.1 | 0 | 0 | 0 | 0 | 200 mm LW CMU w/Fill Insulation | 0.97 | 1.027 |
| wall cts | number 48 | 48 | 0.2 | 3.2 | 10.9 | 14.9 | 14.4 | 12.2 | 9.8 | 7.7 | 6.1 | 4.7 | 3.7 | 2.9 | 2.2 | 1.7 | 1.3 | 1 | 0.8 | 0.6 | 0.5 | 0.4 | 0.3 | 0.2 | 0.2 | 0.1 | 200 mm LW CMU w/Fill Insulation, Gyp. Board | 1.23 | 0.815 |
| wall cts | number 49 | 49 | 1 | 1.1 | 2.6 | 5.1 | 7.3 | 8.4 | 8.6 | 8.3 | 7.7 | 7 | 6.2 | 5.5 | 4.9 | 4.3 | 3.7 | 3.3 | 2.9 | 2.5 | 2.2 | 1.9 | 1.7 | 1.5 | 1.3 | 1.1 | 300 mm LW CMU w/Fill Gyp. Board | 1.44 | 0.695 |
| wall cts | number 50 | 50 | 0.6 | 10.2 | 19.6 | 18.1 | 13.9 | 10.3 | 7.5 | 5.4 | 3.9 | 2.9 | 2.1 | 1.5 | 1.1 | 0.8 | 0.6 | 0.4 | 0.3 | 0.2 | 0.2 | 0.1 | 0.1 | 0.1 | 0 | 0 | Concrete. R-0.9 Board Insulation, Gyp. Board | 1.49 | 0.672 |