Home/Reference Data/Cooling Load Factors/rts_zone_characteristics

Cooling Load Factors: rts_zone_characteristics

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor_type: rts_zone_characteristics3 rows
factor typeitem idconstruction classexterior wallfloorfurnishingspartitionsroof ceiling
rts_zone_characteristicsclass_heavyHeavy100 mm face brick, 200 mm HW concrete air space, 50 mm insulation, 19 mm gyp.Acoustic tile, ceiling air space, 200 mm HW concrete25 mm wood @ 50% of floor area19 mm gyp., 200 mm HW concrete block, 19 mm gyp.200 mm HW concrete, ceiling air space, acoustic tile
rts_zone_characteristicsclass_lightLightSteel siding, 50 mm insulation, air space, 19 mm gyp.Acoustic tile, ceiling air space, 100 mm LW concrete25 mm wood @ 50% of floor area19 mm gyp., air space, 19 mm gyp.100 mm LW concrete, ceiling air space, acoustic tile
rts_zone_characteristicsclass_mediumMedium100 mm face brick, 50 mm insulation, air space, 19 mm gyp.Acoustic tile, ceiling air space, 100 mm HW concrete25 mm wood @ 50% of floor area19 mm gyp., air space, 19 mm gyp.100 mm HW concrete, ceiling air space, acoustic tile