Cooling Load Factors: rts solar

heavy no carpet 10% h20 to heavy no carpet 50% h05

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: rts solar10 rowsPage 3 of 44
factor typeitem idhour (h)rts pct (%)zone type
rts solarheavy no carpet 10% h20202Heavy No Carpet 10%
rts solarheavy no carpet 10% h21212Heavy No Carpet 10%
rts solarheavy no carpet 10% h22222Heavy No Carpet 10%
rts solarheavy no carpet 10% h23231Heavy No Carpet 10%
rts solarheavy no carpet 50% h00027Heavy No Carpet 50%
rts solarheavy no carpet 50% h01113Heavy No Carpet 50%
rts solarheavy no carpet 50% h0227Heavy No Carpet 50%
rts solarheavy no carpet 50% h0335Heavy No Carpet 50%
rts solarheavy no carpet 50% h0444Heavy No Carpet 50%
rts solarheavy no carpet 50% h0554Heavy No Carpet 50%