Cooling Load Factors: rts nonsolar

medium with carpet 50% h01 to medium with carpet 50% h10

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: rts nonsolar10 rowsPage 52 of 56
factor typeitem idhour (h)rts pct (%)zone type
rts nonsolarmedium with carpet 50% h01117Medium With Carpet 50%
rts nonsolarmedium with carpet 50% h0229Medium With Carpet 50%
rts nonsolarmedium with carpet 50% h0335Medium With Carpet 50%
rts nonsolarmedium with carpet 50% h0443Medium With Carpet 50%
rts nonsolarmedium with carpet 50% h0553Medium With Carpet 50%
rts nonsolarmedium with carpet 50% h0662Medium With Carpet 50%
rts nonsolarmedium with carpet 50% h0771Medium With Carpet 50%
rts nonsolarmedium with carpet 50% h0881Medium With Carpet 50%
rts nonsolarmedium with carpet 50% h0991Medium With Carpet 50%
rts nonsolarmedium with carpet 50% h10101Medium With Carpet 50%