Cooling Load Factors: office equip summary

load factor 06 to load factor 14

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: office equip summary9 rowsPage 2 of 2
factor typeitem iddescriptionload factor W per m2 (W/m2)use type
office equip summaryload factor 0611.6 m²/workstation, all desktop use, 1 printer per 107.79medium
office equip summaryload factor 0711.6 m²/workstation, all laptop docking station use, 2 screens, 1 printer per 107.442 screens
office equip summaryload factor 0811.6 m²/workstation, all laptop use, 2 screens, 1 printer per 109.062 screens
office equip summaryload factor 0911.6 m²/workstation, all desktop use, 3 screens, 1 printer per 1010.333 screens
office equip summaryload factor 107.9 m²/workstation, all desktop use, 2 screens, 1 printer per 811heavy, 2 screens
office equip summaryload factor 117.9 m²/workstation, all desktop use, 3 screens, 1 printer per 812.49heavy, 3 screens
office equip summaryload factor 127.9 m²/workstation, all laptop docking use, 2 screens, 1 printer per 8, no diversity12.23full on, 2 screens
office equip summaryload factor 137.9 m²/workstation, all desktop use, 2 screens, 1 printer per 8, no diversity14.35full on, 2 screens
office equip summaryload factor 147.9 m²/workstation, all desktop use, 3 screens, 1 printer per 8, no diversity16.48full on, 3 screens