ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: motor efficiency multi10 rowsPage 5 of 19
factor typeitem idfull load efficiency pct (%)motor kW (kW)motor typenum poles (dimensionless)
motor efficiency multikW186p0 poles2 enclosed95.8186Enclosed2
motor efficiency multikW186p0 poles2 open95186Open2
motor efficiency multikW186p0 poles4 enclosed96.2186Enclosed4
motor efficiency multikW186p0 poles4 open95.8186Open4
motor efficiency multikW186p0 poles6 enclosed95.8186Enclosed6
motor efficiency multikW186p0 poles6 open95.8186Open6
motor efficiency multikW186p0 poles8 enclosed95186Enclosed8
motor efficiency multikW186p0 poles8 open95186Open8
motor efficiency multikW18p5 poles2 enclosed91.718.5Enclosed2
motor efficiency multikW18p5 poles2 open91.718.5Open2