Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Cooling Load Factors: motor efficiency multi

kW7p5 poles4 enclosed to kW90p0 poles4 open

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: motor efficiency multi10 rowsPage 18 of 19
factor typeitem idfull load efficiency pct (%)motor kW (kW)motor typenum poles (dimensionless)
motor efficiency multikW7p5 poles4 enclosed91.77.5Enclosed4
motor efficiency multikW7p5 poles4 open91.77.5Open4
motor efficiency multikW7p5 poles6 enclosed917.5Enclosed6
motor efficiency multikW7p5 poles6 open91.77.5Open6
motor efficiency multikW7p5 poles8 enclosed89.57.5Enclosed8
motor efficiency multikW7p5 poles8 open90.27.5Open8
motor efficiency multikW90p0 poles2 enclosed9590Enclosed2
motor efficiency multikW90p0 poles2 open94.190Open2
motor efficiency multikW90p0 poles4 enclosed95.490Enclosed4
motor efficiency multikW90p0 poles4 open95.490Open4

What else is in Engineering Database

Calculators that use this data

Related data