Cooling Load Factors: lighting power density

lpd 051 to lpd 060

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: lighting power density10 rowsPage 6 of 9
factor typeitem idlpd W per m2 (W/m2)space type
lighting power densitylpd 0517.7Hospital
lighting power densitylpd 0524.4Performing Arts Theater, Dressing Room
lighting power densitylpd 0534.4All other corridors
lighting power densitylpd 0545.3Stairwell
lighting power densitylpd 05512.9Courtroom
lighting power densitylpd 0568.1Post Office, Sorting Area
lighting power densitylpd 05710.1Computer Room
lighting power densitylpd 0585.5<4.6 m²
lighting power densitylpd 0594.1>4.6 m²
lighting power densitylpd 0605.8Fellowship hall