ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: cooking gas hooded10 rowsPage 2 of 4
factor typeitem idapplianceenergy rate standby W (W)energy sourceheat gain sensible Whood typeradiation factor (dimensionless)usage factor (dimensionless)
cooking gas hoodedgas hooded 011Oven: combi: combi-mode*22,185Gas1,758Hooded0.08117
cooking gas hoodedgas hooded 012Convection mode22,185Gas1,700Hooded0.08293
cooking gas hoodedgas hooded 013Convection, full-size12,895Gas3,488Hooded0.27293
cooking gas hoodedgas hooded 014Conveyor (pizza)49,822Gas20,017Hooded0.42,286
cooking gas hoodedgas hooded 015Deck30,772Gas6,008Hooded0.21,026
cooking gas hoodedgas hooded 016Rack mini-rotating*16,500Gas1,319Hooded0.08322
cooking gas hoodedgas hooded 017Pasta cooker*23,446Gas6,946Hooded0.30
cooking gas hoodedgas hooded 018Range top: top off/oven on*7,327Gas2,169Hooded0.3586
cooking gas hoodedgas hooded 0193 burners on/oven off35,169Gas17,614Hooded0.52,081
cooking gas hoodedgas hooded 0206 burners on/oven off35,169Gas35,403Hooded1.013,370