Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Cooling Load Factors: construction material

M10 to M17

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: construction material8 rowsPage 5 of 5
factor typeitem idconductivity W per mK (W/(m·K))density kg per m3 (kg/m3)descriptionlayer idmass kg per m2 (kg/m2)resistance R m2K per W ((m2·K)/W)specific heat kJ per kgK (kJ/(kg·K))thermal capacity kJ per m2K (kJ/(m2·K))thickness mm (mm)
construction materialM100.7801200 mm concrete block (filled)M10162.70.290.92150203.2
construction materialM110.531,281100 mm lightweight concreteM11130.20.190.84109.09101.6
construction materialM120.531,281150 mm lightweight concreteM12195.30.290.84163.64152.4
construction materialM130.531,281200 mm lightweight concreteM13260.40.380.84218.18203.2
construction materialM141.952,243150 mm heavyweight concreteM14341.80.080.92315152.4
construction materialM151.952,243200 mm heavyweight concreteM15455.70.10.92420203.2
construction materialM161.952,243300 mm heavyweight concreteM16683.50.160.92630304.8
construction materialM170.1964150 mm LW concrete roof ballastM1732.50.270.8427.2750.8