Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Cooling Load Factors: construction material

F11 to G02

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: construction material10 rowsPage 2 of 5
factor typeitem idconductivity W per mK (W/(m·K))density kg per m3 (kg/m3)descriptionlayer idmass kg per m2 (kg/m2)resistance R m2K per W ((m2·K)/W)specific heat kJ per kgK (kJ/(kg·K))thermal capacity kJ per m2K (kJ/(m2·K))thickness mm (mm)
construction materialF110.09593Wood sidingF117.50.141.6312.312.7
construction materialF120.041,121Asphalt shinglesF123.60.081.264.473.2
construction materialF130.161,121Built-up roofingF1310.70.061.4715.669.5
construction materialF141.591,922Slate or tileF1424.40.011.2630.6812.7
construction materialF150.04593Wood shinglesF153.80.171.34.896.4
construction materialF160.06368Acoustic tileF1670.320.594.1219.1
construction materialF170.08320CarpetF173.10.121.384.229.5
construction materialF181.82,563TerrazzoF1865.10.010.851.8225.4
construction materialG010.1680116 mm gyp boardG0112.70.11.0913.8515.9
construction materialG020.1154516 mm plywoodG028.60.151.8816.315.9