Home/Reference Data/Transformer Data/OIL_3PH_1000KVA to OIL_3PH_7500KVA

Transformer Data: OIL_3PH_1000KVA to OIL_3PH_7500KVA

Transformer data � ratings, losses, impedance, efficiency, and physical data for oil and dry-type power transformers per IEEE C57.12.00

Electrical Engineeringtransformer_id: OIL_3PH_1000KVA to OIL_3PH_7500KVA5 rows
transformer idefficiency fl pct (%)full load loss W (W)impedance pct (%)kva rating (kVA)no load loss W (W)phase (dimensionless)primary voltage V (V)secondary voltage Vsound level dBA (dBA)total loss W (W)transformer typeweight kg (kg)weight lbs (lbs)x r ratio (dimensionless)
OIL_3PH_1000KVA99.36,50051,000780312470480Y/277597,280oil1,4513,2007
OIL_3PH_150KVA98.81,5003150200312470480Y/277481,700oil3638004
OIL_3PH_2500KVA99.413,0005.752,5001,450312470480Y/2776414,450oil3,0846,80010
OIL_3PH_3750KVA99.518,0005.753,7502,0003345004160Y/24006620,000oil4,3099,50011
OIL_3PH_7500KVA99.532,0006.57,5003,4003345004160Y/24006935,400oil7,25716,00014