Home/Reference Data/Transformer Data/DRY_3PH_112KVA to DRY_3PH_5000KVA

Transformer Data: DRY_3PH_112KVA to DRY_3PH_5000KVA

Transformer data � ratings, losses, impedance, efficiency, and physical data for oil and dry-type power transformers per IEEE C57.12.00

Electrical Engineeringtransformer_id: DRY_3PH_112KVA to DRY_3PH_5000KVA5 rows
transformer idefficiency fl pct (%)full load loss W (W)impedance pct (%)kva rating (kVA)no load loss W (W)phase (dimensionless)primary voltage V (V)secondary voltage Vsound level dBA (dBA)total loss W (W)transformer typeweight kg (kg)weight lbs (lbs)x r ratio (dimensionless)
DRY_3PH_112KVA98.21,6004.5112.53203480208Y/120471,920dry2726003.5
DRY_3PH_15KVA97350315803480208Y/12040430dry681501.5
DRY_3PH_2500KVA99.219,00062,5002,6003480208Y/1206521,600dry2,9486,50010
DRY_3PH_30KVA97.55503.5301203480208Y/12042670dry1022252
DRY_3PH_5000KVA99.334,00065,0004,20034160480Y/2776838,200dry5,21611,50012

This is a sample. Search the full transformer data dataset and 300+ more by creating a free account and accessing the database.