Home/Reference Data/Smoke Control Design/vestibule_pressurization

Smoke Control Design: vestibule_pressurization

Smoke control design parameters per NFPA 92-2021 and IBC 2021 Section 909 — stairwell and elevator pressurization differentials (0.05–0.10 in. w.g.), door opening force limits (30 lbf max), atrium exhaust prescriptive rates (4–6 ACH), axisymmetric and balcony/window plume mass flow equations (NFPA 92 Eq. 4.1, 4.10, 4.12), design fire heat release rates by occupancy (1000–5000 kW), building leakage areas by tightness class (tight/average/loose), door leakage areas, t² fire growth coefficients, tenability criteria (visibility 16–33 ft, temperature 120°C max, CO FED thresholds), and the smoke filling rate formula. Sources: NFPA 92-2021, IBC 2021 Sec. 909, ASHRAE Handbook HVAC Applications Ch. 54, Klote/Milke Handbook of Smoke Control Engineering.

Civil Engineeringsmoke_control_type: vestibule_pressurization1 row
smoke control typerecord iddescriptionnotesunitvalue maxvalue min
vestibule_pressurizationmin_differential_pressureVestibule/Lobby Minimum Pressure DifferentialPressurized vestibule (smoke proof enclosure) differential across each door; must be maintained with any one door open per NFPA 92 testing protocolsin_wg0.10.05

This is a sample. Search the full smoke control design dataset and 300+ more by creating a free account and accessing the database.

Get started for FREE

Related data