Smoke Control Design: design_fire_size

Smoke control design parameters per NFPA 92-2021 and IBC 2021 Section 909 — stairwell and elevator pressurization differentials (0.05–0.10 in. w.g.), door opening force limits (30 lbf max), atrium exhaust prescriptive rates (4–6 ACH), axisymmetric and balcony/window plume mass flow equations (NFPA 92 Eq. 4.1, 4.10, 4.12), design fire heat release rates by occupancy (1000–5000 kW), building leakage areas by tightness class (tight/average/loose), door leakage areas, t² fire growth coefficients, tenability criteria (visibility 16–33 ft, temperature 120°C max, CO FED thresholds), and the smoke filling rate formula. Sources: NFPA 92-2021, IBC 2021 Sec. 909, ASHRAE Handbook HVAC Applications Ch. 54, Klote/Milke Handbook of Smoke Control Engineering.

Civil Engineeringsmoke_control_type: design_fire_size3 rows
smoke control typerecord iddescriptionnotesunitvalue typical
design_fire_sizeassembly_occupancyDesign Fire — Assembly Occupancy (Theater/Arena)Representative steady-state design fire for assembly occupancy without sprinklers; sprinkler-controlled fire HRR at activation is lower; earlier NFPA 92 editions specified 5 MW minimum; current code requires engineering analysiskW5,000
design_fire_sizeoffice_occupancyDesign Fire — Office OccupancyRepresentative design fire for open office; lower fuel load than retail; t² ultra-fast or fast growth often assumedkW1,000
design_fire_sizeretail_occupancyDesign Fire — Retail/Mercantile OccupancyRepresentative design fire for retail; actual value depends on fuel load density and fire growth rate (t² fire); engineer must justify selection per NFPA 92-2021 Sec. 3.2kW2,500

This is a sample. Search the full smoke control design dataset and 300+ more by creating a free account and accessing the database.

Get started for FREE

Related data