Power Cable Pulling: MAX PULLING TENSION

PULL TENSION CU 4AWG to PULL TENSION CU 8AWG

Power cable pulling tension limits, sidewall bearing pressure limits, friction coefficients, jam ratio thresholds, minimum bend radius multipliers, and NEC conduit fill limits. Covers copper (K=0.008) and aluminum (K=0.006) max tension by AWG/kcmil per ICEA P-79-561 / IEEE 1185-2019; SWBP limits for XLPE, EPR, PVC, armored, and lead-sheathed cables; COF by conduit type (steel/PVC/HDPE/FRP) and lubrication condition; jam ratio safe zones (danger: 2.7–3.1); NEC 300.34 bend radius multipliers.

Electrical Engineeringparameter type: MAX PULLING TENSION6 rowsPage 3 of 3
parameter typerecord idcmil area (cmil)conductor materialconductor sizestandardunitvalue max
MAX PULLING TENSIONPULL TENSION CU 4AWG41,740copper4 AWGIEEE 1185-2019 / ICEA P-79-561 S.7.2lbf334
MAX PULLING TENSIONPULL TENSION CU 4 0AWG211,600copper4/0 AWGIEEE 1185-2019 / ICEA P-79-561 S.7.2lbf1,693
MAX PULLING TENSIONPULL TENSION CU 500KCMIL500,000copper500 KCMILIEEE 1185-2019 / ICEA P-79-561 S.7.2lbf4,000
MAX PULLING TENSIONPULL TENSION CU 6AWG26,240copper6 AWGIEEE 1185-2019 / ICEA P-79-561 S.7.2lbf210
MAX PULLING TENSIONPULL TENSION CU 750KCMIL750,000copper750 KCMILIEEE 1185-2019 / ICEA P-79-561 S.7.2lbf6,000
MAX PULLING TENSIONPULL TENSION CU 8AWG16,510copper8 AWGIEEE 1185-2019 / ICEA P-79-561 S.7.2lbf132