Power Cable Pulling: MAX_PULLING_TENSION

Power cable pulling tension limits, sidewall bearing pressure limits, friction coefficients, jam ratio thresholds, minimum bend radius multipliers, and NEC conduit fill limits. Covers copper (K=0.008) and aluminum (K=0.006) max tension by AWG/kcmil per ICEA P-79-561 / IEEE 1185-2019; SWBP limits for XLPE, EPR, PVC, armored, and lead-sheathed cables; COF by conduit type (steel/PVC/HDPE/FRP) and lubrication condition; jam ratio safe zones (danger: 2.7–3.1); NEC 300.34 bend radius multipliers.

Electrical Engineeringparameter_type: MAX_PULLING_TENSION3 rows
parameter typerecord idcmil area (cmil)conductor materialconductor sizenotesunitvalue max
MAX_PULLING_TENSIONPULL_TENSION_AL_1000KCMIL1,000,000aluminum1000_KCMILT_max=0.006*CMA per conductorlbf6,000
MAX_PULLING_TENSIONPULL_TENSION_AL_1_0AWG105,600aluminum1/0_AWGT_max=0.006*CMA per conductor; Al min size is typically 1/0 per NEC 310.14lbf634
MAX_PULLING_TENSIONPULL_TENSION_AL_250KCMIL250,000aluminum250_KCMILT_max=0.006*CMA per conductorlbf1,500

This is a sample. Search the full power cable pulling dataset and 300+ more by creating a free account and accessing the database.

Get started for FREE